New Product Release-WE-T01 Internet of Things Collection and Transmission Device

Posted in 新品资讯  |  Tagged , , , ,

Product Features

WE-T01 IoT collection and transmission equipment is mainly applied toFire Alarm Controllersystem, electrical fire system, door magnet system and other fire equipment systems that may be accessed later. This product is mainly applied to fire IOT data acquisition and communication. The hardware interface of this product collects isolation design, EMC and anti-RF interference and other protection design, and the input module of this product supports RS232, RS485, passive switch quantity; supportsRJ45Wired,4GFull network signal upload method.

specificities

  • Multi-communication mode design to maximize the smoothness of the network data
  • Supports self-diagnosis and restoration of normal Internet access after disconnection and reconnection
  • Module information can be configured remotely, easy to use and maintain
  • With the function of remote rebooting equipment, upgrading software version.
  • Automated go-live, full network configuration and debugging mode to simplify installation and maintenance processes

System design principles

the normative principle

System in accordance with national standardsGB 26875.3-2011 City Fire Remote Monitoring SystemRe: Design, construction and acceptance of the communication protocol portion of the alarm transmission network.

The principle of networking

At present, most of the automatic fire alarm systems in domestic cities are in the stage of independent alarm of each building, without unified fire management, unable to complete the functions of urban fire equipment management, fire alarm management, security management and fire watchman management. With the application of Internet of Things technology in China, the system is an open cross-regional networked computer integrated automation control and management system, which really plays a role in protecting people's life and property safety.

The principle of progress

The system structure design, system configuration and system management method adopt international advanced and at the same time mature and practical technologies. It adopts advanced development technology and provides advanced business management means to realize networked and scientific management of automatic fire alarm and user automatic alarm equipment and duty personnel.

reliability principle

Stability requirements are to ensure that the system can run continuously and stably. Guarantee 7 × 24 hours of stable operation and service; the whole system has a perfect recovery mechanism for sudden abnormalities.

economic principle

The system design will take full account of the market economic principles, in the selection of products, in accordance with the reliable and applicable, moderate, appropriate principles of configuration, under the premise of ensuring the safety and reliability of the system, to ensure that the system has a high performance-price ratio, to fully guarantee the interests of the owners of the network and the investor.

Ease of use principle

Ease of use is a requirement for the operability and manageability of the system. Application of simple, intuitive, the user in the use of a glance, easy to quickly master the product operation method, especially suitable for the way of thinking and work habits of engineers. Currently compatible with all types of mainstream fire alarm equipment access, with easy installation, simple commissioning and strong compatibility.

system parameter

system function

1. Receiving and transmitting function of fire alarm information

User information transmission deviceReceive fire alarm information from the fire detection and alarm system of networked users and transmit the information to the monitoring center within 10s.

2. The function of receiving and transmitting information on the operation status of the building fire protection facilities.

The user information transmission device receives the operation status information of the fire protection facilities from the networked users' buildings (except the fire alarm information) and transmits the information to the monitoring center within 10s.

3. Manual alarm function

The user information transmission device is provided with a manual alarm button. When the manual alarm button is actuated, the transmission device can transmit the manual alarm information to the monitoring center within 10s. Manual alarm operation and transmission have the highest priority.

4. Inspection and checking function

The user information transmission device receives the inspection instruction from the monitoring center and transmits the relevant operation status information of the transmission device to the monitoring center according to the instruction. At the same time, the user information transmission device receives the duty personnel checking instruction from the monitoring center and responds to it by means of the set checking response button.

5. Fault alarm function

The user information transmission device has a local fault alarm function and transmits the corresponding fault information to the monitoring center.

6. Self-test function

The User Information Transmission Unit has the function of manually checking whether all the indicators, displays, alarm sound devices and communication lines of the panel of the unit are normal.

7. Main and standby power switching function

The user information transmission device has the function of automatic switching between main and standby power supply;

Device Interface Interface